Engineering Data |
|
Electrical Specifications: |
|
Control Specifications: |
|
Environmental Specifications: |
|
Physical Attributes: |
|
Protective Features: |
|
* Programmable motor overload protection to comply with N.E.C. Article 430 * Drive overload protection to protect inverter * Motor stall protection at acceleration / deceleration and constant speed operation * Peak output current monitoring to protect against line-to-line shorts and line-to-ground shorts * Ground fault monitoring * Heatsink over-temperature monitoring * AC line over-voltage protection * DC bus over-voltage protection * DC bus under-voltage protection * Programmable stall protection * Control power ride-thru 2 seconds or greater, depending on load * Internal power supply monitoring * AC power loss detection * Critical speed rejection with programmable 3 points with bandwidth to avoid mechanical resonance * Flycatcher “catch a spinning motor” * Password protection to prevent parameter changes by unauthorized personnel * 4 to 20ma reference loss detection * Programmable thresholds and more |
|
Control I/O: |
|
Standard Drives Features: |
|
* New generation IGBT * Nema type 1 (IP20) as standard for all models * 50°C ambient with standard Nema 1 type 1 (IP20) enclosure * High voltage ratings: 250Vac + 10%, 500Vac + 10% models, and 600Vac + 10% models * Built-in power factor correction DC reactor for all models above 20 Hp * Modbus RTU & Metasys N2 serial communications ready * Input line suppression: Metal oxide varistors for line-to-line and line-to-ground voltage surge protection * Build-in radio frequency filter * Nonvolatile parameter storage * All parameters are saved in EEPROM (nonvolatile) * Autologging fault history: ten last faults recorded in order of occurrence * Internal control diagnostics * Simple programming through the Real-time Operator Module (R.O.M.) with all data entries and monitoring in engineering units with English descriptions * Setpoint Control P.I.D. * Injection DC Braking with braking time calculated automatically by the drive * Critical speed rejection * Programmable auto-restart * Fixed or variable carrier (programmable) * Programmable “Total Drive Run Time” accumulator * Parameter security code * User definable displays with programmable format and parameter scaling * 7 programmable digital inputs for custom setups * Metering: AC line voltage, motor current, motor voltage, DC Bus voltage, Kw, Kwh, running Kwh cost, and more… * 8 programmable digital preset speeds with user selectable acceleration and deceleration rates * M.O.P. function * Programmable PWM carrier frequency, fixed or variable * Programmable thresholds * Programmable maintenance timers * Bi-directional auto-speed search (flycatcher) for starting into rotating loads * S-curve accel / decel control * Programmable time delay and logic functions (AND, OR, NOR) of bit parameters, digital inputs and outputs * Adding, subtracting, multiplying, dividing, ramping, limiting, and/or filtering functions of parameters and analog inputs and outputs * Parameters can be displayed, routed to an analog/digital output, or re-routed and used as an input parameter to control another function within the drive * User programmable functions and modes * Open Loop or closed-loop control operation easy setup * Precise control of motor speed and torque * Rigid and non-rigid position control including orientation |
|
Phoenix EX |
|
Home |
|
Contact Us |
|
Product List |
|
Downloads |
|
Applications |
|
Photo Gallery |
|
Home |
|
Contact Us |
|
Product List |
|
Downloads |
|
Applications |
|
Photo Gallery |
|
For more information |
|
US Drives, Inc. |






|
Rated Input Voltage:
Frequency Tolerance: Number of Phases: Displacement Power Factor: Efficiency: Max. Short Circuit Current Ratings: |
200-250VAC, 380-500Vac, 500-600Vac -10% of minimum, +10% of maximum 48-63 Hz 3 .95 or greater 97% or greater at rated current 200,000A rms symmetrical, 600 volts (when used with AC input line fuses specified in tables 1-1 to 1-3) |
|
Control Method:
Output Voltage: Output Frequency Range: Frequency Accuracy:
Frequency Resolution:
Accel/Decel: Drive Overload:
Inverse Time Overload:
Current Limit: Braking Torque: Maximum Connected Motor: Control Power Ride-Thru: |
Sine coded PWM with programmable carrier Space Vector Control 0 to rated voltage 0 to 600 Hz Analog reference: 0.1% of max frequency Digital reference: 0.01% of max frequency Analog reference: 0.06Hz at 60Hz Digital reference: 0.001Hz at 60Hz 0.1 to 3276 sec. At Constant Torque:150% of drive rated output for 1 minute At Variable Torque:120% of drive rated output for 1 minute Programmable motor overload protection to comply with N.E.C. Article 430 Proactive current limit programmable in % of motor rated current Approximately 20% 2 times rated drive horsepower 2 seconds or greater, depending on load |
|
Ambient Temperature: Storage Temperature: Altitude: Humidity: Vibration: Immunity:
Input R.F.I. Filter: |
-10°C to 50°C (14°F to 122°F) Nema type 1 enclosed -40°C to 70°C (-40°F to 158°F) Nema type 1 enclosed Sea level to 3300 Feet [1000m] without derating 95% relative humidity non-condensing 9.8m/sec2 (1.0G) peak IEEE C62.41-1991 Category B (Formally known as IEEE 587) EN50082-2 (Generic Immunity Standard) Standard on all models |
|
Mounting:
Nema Rating: Construction: |
Through hole or panel mount for size 0 to size 3 drives Size 4 drives are free standing enclosure Type 1 (IP20) as standard, Type 12 (IP54) optional Steel construction (reduces E.M.I.) |
|
8 Digital Inputs:
2 Digital Outputs: 2 Analog Inputs:
2 Analog Output: 1 Voltage Reference: 24VDC Source: |
7 user programmable inputs and 1 dedicated input for “Stop”, rated for 24VDC logic control 2 programmable dry contacts rated 115Vac @ 5A; 30VDC @ 3.5A -10 to +10V (10 bits) with input impedance: 75KΩ, or 4-20 mA @ 500Ω - Programmable -10 to +10V (10 bits) @ 2 mA max; output impedance = 100Ω -Programmable 15VDC reference @ 10 mA max Use to power operator pushbuttons and US Drives option boards: 24VDC @ 80 mA max |