Engineering Data

To contact us:

Tel: 1-716-731-1606

E-Mail: sales@usdrivesinc.com

Electrical Specifications:

Control Specifications:

Environmental Specifications:

Physical Attributes:

Protective Features:

* Programmable motor overload protection to comply with N.E.C. Article 430

* Drive overload protection to protect inverter

* Motor stall protection at acceleration / deceleration and constant speed operation

* Peak output current monitoring to protect against line-to-line shorts and line-to-ground shorts

* Ground fault monitoring

* Heatsink over-temperature monitoring

* AC line over-voltage protection

* DC bus over-voltage protection

* DC bus under-voltage protection

* Programmable stall protection

* Control power ride-thru 2 seconds or greater, depending on load

* Internal power supply monitoring

* AC power loss detection

* Critical speed rejection with programmable 3 points with bandwidth to avoid mechanical resonance

* Flycatcher “catch a spinning motor”

* Password protection to prevent parameter changes by unauthorized personnel

* 4 to 20ma reference loss detection

* Programmable thresholds and more

Control I/O:

Standard Drives Features:

* New generation IGBT

* Nema type 1 (IP20) as standard for all models

* 50°C ambient with standard Nema 1 type 1 (IP20) enclosure

* High voltage ratings: 250Vac + 10%, 500Vac + 10% models, and 600Vac + 10% models

* Built-in power factor correction DC reactor for all models above 20 Hp

* Modbus RTU & Metasys N2 serial communications ready

* Input line suppression: Metal oxide varistors for line-to-line and line-to-ground voltage surge protection

* Build-in radio frequency filter

* Nonvolatile parameter storage

* All parameters are saved in EEPROM (nonvolatile)

* Autologging fault history: ten last faults recorded in order of occurrence

* Internal control diagnostics

* Simple programming through the Real-time Operator Module (R.O.M.) with all data entries and monitoring in engineering units with English descriptions

* Setpoint Control P.I.D.

* Injection DC Braking with braking time calculated automatically by the drive

* Critical speed rejection

* Programmable auto-restart

* Fixed or variable carrier (programmable)

* Programmable “Total Drive Run Time” accumulator

* Parameter security code

* User definable displays with programmable format and parameter scaling

* 7 programmable digital inputs for custom setups

* Metering: AC line voltage, motor current, motor voltage, DC Bus voltage, Kw, Kwh, running Kwh cost, and more…

* 8 programmable digital preset speeds with user selectable acceleration and deceleration rates

* M.O.P. function

* Programmable PWM carrier frequency, fixed or variable

* Programmable thresholds

* Programmable maintenance timers

* Bi-directional auto-speed search (flycatcher) for starting into rotating loads

* S-curve accel / decel control

* Programmable time delay and logic functions (AND, OR, NOR) of bit parameters, digital inputs and outputs

* Adding, subtracting, multiplying, dividing, ramping, limiting, and/or filtering functions of parameters and analog inputs and outputs

* Parameters can be displayed, routed to an analog/digital output, or re-routed and used as an input parameter to control another function within the drive

* User programmable functions and modes

 

Phoenix DX

Rated Input Voltage:

200-250Vac, 380-500Vac, 500-600Vac           -10% of minimum, +10% of maximum.

Frequency Tolerance:

48-63 Hz

Number of Phases:

3

Displacement Power Factor:

.95 or greater

Efficiency:

97% or greater at rated current

Max. Short Circuit Current Rating:

200,000A rms symmetrical, 600 volts (when used with AC input line fuses specified in tables 1-1 to 1-3).

Control Method:

Space Vector control. 

Output Voltage:

0 to rated voltage.

Output Frequency Range:

0 to 600 Hz.

Frequency accuracy:

Analog reference: 0.1% of max frequency.

Digital reference: 0.01% of max frequency.

Frequency resolution:

Analog reference: 0.06Hz at 60Hz.

Digital reference: 0.001Hz at 60Hz.

Accel/Decel:

0.1 to 3276 sec.

Drive overload:

At Constant Torque:  150% of drive rated output for 1 minute.

At Variable Torque:  120% of drive rated output for 1 minute.

Inverse Time Overload:

Programmable motor overload protection to comply with N.E.C. Article 430.

Current limit:

Proactive current limit programmable in % of motor rated current.

Braking torque:

Approximately 20%.

Maximum connected motor:

2 times rated drive horsepower.

Control power ride-thru:

2 seconds or greater, depending on load.

Ambient Temperature:

-10°C to 50°C (14°F to 122°F) Nema type 1 enclosed

Storage Temperature:

-40°C to 70°C (-40°<