Engineering Data |
|
Electrical Specifications: |
|
Control Specifications: |
|
Environmental Specifications: |
|
Physical Attributes: |
|
Protective Features: |
|
* Programmable motor overload protection to comply with N.E.C. Article 430 * Drive overload protection to protect inverter * Motor stall protection at acceleration / deceleration and constant speed operation * Peak output current monitoring to protect against line-to-line shorts and line-to-ground shorts * Ground fault monitoring * Heatsink over-temperature monitoring * AC line over-voltage protection * DC bus over-voltage protection * DC bus under-voltage protection * Programmable stall protection * Control power ride-thru 2 seconds or greater, depending on load * Internal power supply monitoring * AC power loss detection * Critical speed rejection with programmable 3 points with bandwidth to avoid mechanical resonance * Flycatcher “catch a spinning motor” * Password protection to prevent parameter changes by unauthorized personnel * 4 to 20ma reference loss detection * Programmable thresholds and more |
|
Control I/O: |
|
Standard Drives Features: |
|
* New generation IGBT * Nema type 1 (IP20) as standard for all models * 50°C ambient with standard Nema 1 type 1 (IP20) enclosure * High voltage ratings: 250Vac + 10%, 500Vac + 10% models, and 600Vac + 10% models * Built-in power factor correction DC reactor for all models above 20 Hp * Modbus RTU & Metasys N2 serial communications ready * Input line suppression: Metal oxide varistors for line-to-line and line-to-ground voltage surge protection * Build-in radio frequency filter * Nonvolatile parameter storage * All parameters are saved in EEPROM (nonvolatile) * Autologging fault history: ten last faults recorded in order of occurrence * Internal control diagnostics * Simple programming through the Real-time Operator Module (R.O.M.) with all data entries and monitoring in engineering units with English descriptions * Setpoint Control P.I.D. * Injection DC Braking with braking time calculated automatically by the drive * Critical speed rejection * Programmable auto-restart * Fixed or variable carrier (programmable) * Programmable “Total Drive Run Time” accumulator * Parameter security code * User definable displays with programmable format and parameter scaling * 7 programmable digital inputs for custom setups * Metering: AC line voltage, motor current, motor voltage, DC Bus voltage, Kw, Kwh, running Kwh cost, and more… * 8 programmable digital preset speeds with user selectable acceleration and deceleration rates * M.O.P. function * Programmable PWM carrier frequency, fixed or variable * Programmable thresholds * Programmable maintenance timers * Bi-directional auto-speed search (flycatcher) for starting into rotating loads * S-curve accel / decel control * Programmable time delay and logic functions (AND, OR, NOR) of bit parameters, digital inputs and outputs * Adding, subtracting, multiplying, dividing, ramping, limiting, and/or filtering functions of parameters and analog inputs and outputs * Parameters can be displayed, routed to an analog/digital output, or re-routed and used as an input parameter to control another function within the drive * User programmable functions and modes
|
|
Phoenix DX |



|
Rated Input Voltage: |
200-250Vac, 380-500Vac, 500-600Vac -10% of minimum, +10% of maximum. |
|
Frequency Tolerance: |
48-63 Hz |
|
Number of Phases: |
3 |
|
Displacement Power Factor: |
.95 or greater |
|
Efficiency: |
97% or greater at rated current |
|
Max. Short Circuit Current Rating: |
200,000A rms symmetrical, 600 volts (when used with AC input line fuses specified in tables 1-1 to 1-3). |
|
Control Method: |
Space Vector control. |
|
Output Voltage: |
0 to rated voltage. |
|
Output Frequency Range: |
0 to 600 Hz. |
|
Frequency accuracy: |
Analog reference: 0.1% of max frequency. Digital reference: 0.01% of max frequency. |
|
Frequency resolution: |
Analog reference: 0.06Hz at 60Hz. Digital reference: 0.001Hz at 60Hz. |
|
Accel/Decel: |
0.1 to 3276 sec. |
|
Drive overload: |
At Constant Torque: 150% of drive rated output for 1 minute. At Variable Torque: 120% of drive rated output for 1 minute. |
|
Inverse Time Overload: |
Programmable motor overload protection to comply with N.E.C. Article 430. |
|
Current limit: |
Proactive current limit programmable in % of motor rated current. |
|
Braking torque: |
Approximately 20%. |
|
Maximum connected motor: |
2 times rated drive horsepower. |
|
Control power ride-thru: |
2 seconds or greater, depending on load. |
|
Ambient Temperature: |
-10°C to 50°C (14°F to 122°F) Nema type 1 enclosed |
|
Storage Temperature: |
-40°C to 70°C (-40°< |