Regen Module Specifications

To contact us:

Tel: 1-716-731-1606

E-Mail: sales@usdrivesinc.com

AC Line Regenerative Module

* Turns Any Standard PWM AC Drive Into a Line Regenerative AC Drive

* May Be Used With Any Manufacturers “Fixed Bridge” Type PWM AC Drive

* Only Five Wires To Connect – Two DC Bus Leads and Three AC Power Leads

* High Horsepower Applications up to 1750 HP

* Absolutely No Set Up Is Required

* Highest Efficiency – Better Than 99% Efficient

* Automatic Fault Clearing

* Phase Insensitive

* Nema Type 1 Metal Enclosure (Reduces EMI)

* Micro Processor Based Digital Control Circuitry

* Surface Mount Printed Circuit Boards

* Latest Generation IGBT Power Devices

* Customer Inputs - Module Enable and Module Reset (jumpered for most applications)

* Customer Output – Regen Module On – Form C Dry Contact rated 5 Amps at 115VAC

* Meter Output Signal - Proportional To DC Regen Current

* Line Voltage Surge Protection - Transients to 6000V - Meets IEEE C62.41-1991 Cat B

* High Electrical Noise Immunity – Meets EN50082-1,2 – Showering Arc, 2000 V Peak

* 55°C Maximum Ambient Temperature Rating

* Indicating Light Emitting Diodes For:

                    Regenerative Module Active

                    Regenerative Module In Current Limit

                    Power Supply Status

                    D.C. Bus Charged

                    Over-Voltage

                    Under-Voltage

                    Instantaneous Over Current

                    Phase Loss

                    Over Temperature

Electrical

 

Rated Input Voltage: 
 

Rated Input Frequency:
Noise Immunity: 
 

Surge Protection:
 
Efficiency:

200-250VAC, 380-500VAC, 500-600VAC
-10% of minimum, +10% of maximum 
47 to 63HZ
Showering Arc - 2000V peak
EN50082-1,2 
Line Transients to 6000V
IEEE C62.41-1999 Category B
Greater than 99%

Control

 

Logic Inputs: 
 
Logic Output: 
 
Analog Output:

Regenerative Module Enable
Regenerative Module Reset
Form “C” Relay Contacts Rated 115Vac @ 5Amps, 30VDC @ 3.5Amps
(Relay Energized When Regenerative Module is “Active”)
100uA meter output indicating Regenerating DC amps

Environmental

 

Ambient Temperature:
Storage Temperature: 
Altitude: 
Humidity: 
Vibration:

14°F to 131°F (-10°C to 55°C) without Derating
-40°F to 158°F (-40°C to 70°C)
Sea Level to 3,300 Feet(1000m) w/o Derating
95% Relative Humidity (Non condensing)
9.8 m/s2 (1.0G) or Less

Physical Attributes

 

Mounting: 
Nema Rating: 

Construction:

Through Hole or Panel Mount
Type 1 (IP-20) as Standard, Type 12 (IP-54) Optional
Rugged Heavy Gauge Steel (Reduces E.M.I.)

Indicators

 

L.E.D.’s:

Regen Active
Regen In Current Limit
Power Supply Status
D.C. Bus Charged
Over Voltage
Under Voltage
Instantaneous Over Current
Phase Loss
Over Temperature

Sizing

 

For 150% Braking Torque at Maximum Speed use the following formulas:
Continuous DC Amps = Drive Horsepower x 2.0 @ 240VAC 
Continuous DC Amps = Drive Horsepower x 1.1 @ 480VAC 
Continuous DC Amps = Drive Horsepower x 0.9 @ 575VAC